The following is an example of a calculation of ventilation requirements for a battery room with lead acid batteries. Lead acid batteries release hydrogen during charging as well as on float (trickle charge after the full charge). Hydrogen concentration above 5% is not a safe situation. A spark can create explosion when the hydrogen concentration is high. The following procedure explains ventilation requirements for a battery room to keep the hydrogen concentration below 1%.
This following calculation will show you the ventilation requirements during normal float conditions.
During abnormal conditions higher ventilation may be required depending upon the condition.
Amount of hydrogen release during normal float condition for a flooded battery is given as
VHy (cubic feet per hour) = 0.0148 x FC (where FC is float current in Amps)
If the battery room has N number of cells then the total volume of hydrogen released per hour
VTHy = VHy x N (cubic feet/hour)
Let us assume the free volume of the battery room is Vr (cubic feet)
(free volume is the actual volume of the room minus the volume taken by objects in the room including batteries)
Time required to reach 1% concentration of hydrogen t = Vr/100 VTHy.
In other words complete air exchange is required in every t hours is enough ventilation to keep the hydrogen concentration below 1%.
Higher charge voltage, temperature, thermal runaway, overcharge condition will significantly affect the hydrogen generation rate of a lead acid battery. Care should be taken to accommodate all the possible abnormal conditions.
If you have any questions feel free to contact us at (877)394-3941.
This following calculation will show you the ventilation requirements during normal float conditions.
During abnormal conditions higher ventilation may be required depending upon the condition.
Amount of hydrogen release during normal float condition for a flooded battery is given as
VHy (cubic feet per hour) = 0.0148 x FC (where FC is float current in Amps)
If the battery room has N number of cells then the total volume of hydrogen released per hour
VTHy = VHy x N (cubic feet/hour)
Let us assume the free volume of the battery room is Vr (cubic feet)
(free volume is the actual volume of the room minus the volume taken by objects in the room including batteries)
Time required to reach 1% concentration of hydrogen t = Vr/100 VTHy.
In other words complete air exchange is required in every t hours is enough ventilation to keep the hydrogen concentration below 1%.
Higher charge voltage, temperature, thermal runaway, overcharge condition will significantly affect the hydrogen generation rate of a lead acid battery. Care should be taken to accommodate all the possible abnormal conditions.
If you have any questions feel free to contact us at (877)394-3941.
Nice information! Its useful for all. Thanks for sharing your information.
ReplyDeleteLead acid battery manufacturers,Lead acid battery manufacturers in Coimbatore
Your post is very nice. useful information. Thanks for sharing.
ReplyDeleteI have a page on Lead oxide Manufacturers
Visit my page here
Lead Ingots Manufacturers
Very interesting post. Thanks for sharing it! It is always a joy to learn something that I didn't know. I have you to thank for teaching me something new, and I appreciate it very much. :-)
ReplyDeletesee here my post topic on Lead acid batteries manufacturers
Recycled PP granules Manufacturers
Online UPS System iElectrical is an online subsidiary of Computer & Telecom Specialists (CTS). CTS specializes in tailoring Turn-Key Project Solutions.
ReplyDeleteGreat Post, I read it well. very useful info Thank you so much for sharing this one really well defined all peaceful information Lead acid battery manufacturers in bangalore | Inverter battery supplier
ReplyDelete